Thermostat Basic Programming Tips
|
Four Button Stats (flat, vertical, star)
Set Clock: Mode + Up for 2 sec, use Up and Down to adjust, add Fan/Override to adjust by hrs. Program: Mode + Up for 2 sec Setup: Mode + Fan / Override together for 7 seconds (2 for older models) Calibrate: Mode + Down for 2 sec, then Mode, then adjust temp with Up or Down button, then Mode Outside Air Temp: Mode for 2 sec (not available on all models) Factory Reset: Mode + Down for 2 sec, then Fan/Override for 2 sec until display either blinks or says Fd, then Mode, then Mode 50/60 Hz: Mode + Down (2 sec), then Mode, then Fan/Override (5 sec), will say 50 or 60, Mode. Emergency Heat: Fan + Up for 2 sec
|
Eight Button Status (Slimline Platinum)
Set Clock: Set Clock button, use Up and Down to adjust time, add Fan/Override to adjust by hours, Mode to get to day set, Set Clock to exit Program: Program button Setup: Mode + Program, if not Program button, then Mode + Backlight Calibrate: Mode + Fan for 7 sec, then Up + Down, then Up + Down again, then adjust temp with Up or Down button, then Mode Outside Air Temp: Outside button, if no Outside, then Mode for 2 sec (N/A on some models) Factory Reset: Mode + Fan for 7 sec, then Fan for 2 sec until display either blinks or says Fd, then Mode, then Mode 50/60 Hz: Mode + Fan (5 sec), Up + Down, Up + Down, then three bottom right buttons together, will say either 50 or 60, then Mode to exit. Emergency Heat: Fan + Up for 2 sec
|
Special Features List:
Residential Models T1050 - 5+2 program (weekday/weekend) T1000FM - Single day program, adj. Service filter indicator T1100FM - 7 day program, Programmable Fan (hrs restriction added- date code 99), vacation, Energy Watch for cooling & heating (counts hours), Service Filter T1100FM - Wireless - 500 ft range, 64 house codes, up to 4 stats per receiver, NO service filter, NO emergency heat, AA Lithium batteries
Commercial Models T2100 / T2700 - Non-programmable, dry contact input (NO or NC), soft start, 3 security levels, 4 hr override
T2800 - 7 day programmable, Holiday, 3 sec levels w/ setpoint limiting
T2900 - 220 features plus remote sensor capability, dry contact, soft start, pre-occupancy purge, economizer control (99 date codes)
All programmable commercial stats have: 48 hr clock protection, 4 hr adj. override and smart fan.
|
Standard Features On All Stats:
Large display, dual setpoint, 1-for-all design - works on almost all types of equipment, no mercury, no batteries, non-volatile memory, continuously lit backlight, adjustable time guards, keypad lock
Commercial Program: always press Mode to go to the next step, Up or Down to change setting.
To enter program mode: 4 button stats press Mode + Up for 2 sec, 8 button stats press Program button
Note: If no buttons are pushed for 1 minute, thermostat will automatically return to normal operation.
|
- Occupied 1 - can set up to 3 occupied periods per day. Normally set to one.
- Occupied cool temperature setting
- Occupied heat temperature setting
- Unoccupied cool temperature setting
- Unoccupied heat temperature setting
- M - choose what day you are programming - normally start with M
- Start time for Occupied 1 for Monday
- Stop time for Occupied 1 for Monday
- On/Off - Does occupied 1 to run at all on Monday? No means unoccupied all day
- - If you set more than one Occupied period in step 1, now you will repeat steps 2,3,7,8,and 9 for Occupied 2 and 3
- Copy - Copy the program from the previous day, yes or no.
- - if YES, Monday's schedule will be copied to Tuesday
- - if NO, program different schedule for Tuesday (steps 7,8,and 9)
- Repeat step 10 until finished, then exit the program mode the same way you entered it.
|
Residential Program: always press Mode to go to the next step, Up or Down to adjust.
To enter program mode: 4 button stats press Mode + Up for 2 sec, 8 button stats press Program button
Note: If no buttons are pushed for 1 minute, thermostat will automatically return to normal operation.
Following program is for 7 day models. Single or 5-2 will have fewer steps.
|
- M - choose what day to program - normally M (Monday)
- Morning period start time
- Morning period cool temperature setting
- Morning period heat temperature setting
- Day period - repeat steps 2,3, and 4
- Evening period - repeat steps 2,3, and 4
- Night period - repeat steps 2,3 and 4
- Copy - Copy the program from the previous day, yes or no.
- - if YES, Monday's schedule will be copied to Tuesday
- - if NO, program different schedule for Tuesday (repeat steps 2-7)
- Repeat step 8 until finished, then exit the program mode the same way you entered it.
|
|
|
|
|
|
|
|