34 IGNITION PROVING FAULT - Control will try three more times before
lock out #14 occurs
Check for: - Gas valve defective or gas valve or turned off Manual valve
shut-off.
Defective Hot Surface Ignitor, Low inlet gas pressure, Flame sensor must
be ungrounded.
Green wire MUST be connected to furnace sheet metal
Proper flame sense micro amps (.5 microamps D.C. minimum, 4.0 - 6.0
nominal in HIGH HEAT)
Inadequate flame carryover or rough ignition. Oxide buildup on flame
sensor (clean with fine steel wool)