31 HIGH PRESSURE SWITCH FAULT - Indicates high pressure switch is
closed at call, or in low heat,
or fails to close after call, or opens in high heat.
Check for: - Plugged condensate drain.
- Water in vent piping, possibly sagging pipe.
- Improper pressure switch wiring or pressure switch tubing connections.
- Failed or "Out-of-Calibration" pressure switches.
32 LOW PRESSURE SWITCH FAULT - Indicates low pressure switch is
closed at call, or fails to close
after call, or opens during operation.
Check for: - Plugged condensate drain.
- Water in vent piping, possibly sagging pipe.
- Improper pressure switch wiring or pressure switch tubing connections.
- Failed or "Out-of-Calibration" pressure switches